CASE STUDIES Single to Three phase POLYPHAZ Rotary converters
Pumping

Palmers Winery Margaret river Western Australia

A strata titled winery comprising of 37 free hold vineyard blocks , with sites ranging from 2 hectares to 5 hectares all irrigated via a central lake, three phase power was out of the question and a generator set was not a viable option to operate the two 15kw submersible pumps laid on their sides to irrigate the vines via the lake.

 
        2 x 15kw submersible pumps                     2 x R/37/480 rotary converters



N. Elson Karrivale Western Australia

Three phase power was required to operate the 22KW submersible pump at this rural location, however was many Kilometers away & several thousand dollars to get connected.
A rotary converter was specified / selected as a good voltage balance is required to operate submersible pump.


        R/37/480hd rotary converter                                22kw submersible pump
 

                                                     Bantry  Bay Vineyard


Irrigation was previously supplied via 2 x 15 kw 3 phase pumps operated via 2 x electronic inverters for approx. three years during this time they have replaced four Western Power supply transformers due to Harmonics, along with other problems like contactor coils running hot & melting ,the switchboard running hot all typical indications of harmonics.

They needed to upgrade the irrigation to 3 x 22kw pumps operated via one of the existing VSDs to control pressure , we offered the R/75/480U rotary converter to supply 415 volt three phase from their 480 volt single phase supply with standout results in the form of: efficiency, voltage & current asymmetry with none of the effects of harmonics apparent.

How we achieved these results:
 

                    1   High efficiency
                    2   Low circulating currents
                    3   Lower power costs
                    4   Low harmonics... throughout the load spectrum
                    5   High power factor  
              Swordfish pump controller                                           3 x 22 kw pump motors


POLYPHAZ  R/75/480U  Rotary converter


Power supplied via 2 x 100KVA TXs

                                                    Reading taken Dated 21/01/2003



        Input readings
Supply voltage no load:    481volts
Supply voltage full load:   465volts
Full load current @ 465volt single phase:    150amps

        Output readings
Output voltage asymmetry
L1>L2    409
L1>L3    403
L2>L3    395

Pump 1 current reading                Pump 2 current reading            Pump 3 current reading
L1    34amps                               L1    37amps                           L1    34amps
L2    32amps                               L2    32amps                           L2    34amps
L3    34amps                               L3    36amps                           L3    34amps
 
 