NeuTrak  balanced output supply to neutral


For some time now we have been offering the VolTrak system as standard equipment from R/15 rotary converters up as a standard feature with good customer feed back , this system gives a asymmetrical supply across phases ( balanced voltages across the three phases )  however there is a increasing demand for a balanced output supply with reference to neutral e.g.: on a 415 volt three phase system you would have
L1 > neutral  240volt, L2 > neutral 240volt, L3 > neutral 240volt.

A/C units and a growing amount of machine tools will not operate with unbalanced voltage to neutral , as a result of this we can now offer the NeuTrak system as a option form rotary converters R/15 up .
                                                       
                                                        

floating pole    

Rotary converter have a higher voltage to neutral on the generate or center phase usually in the order of  x 1.73 & as three phase motors do not reference to neutral this is not a problem , however in the cases of machinery that has supply monitoring this can present a problem also machinery that has several motors on different phases and several types of specialized machinery.

Neutrak Case Study

Vinlines mobile bottling plant is made up of a mix of single & three phase loads totaling aprox 11kw , it is not practical to rewire the bottling plant to suit the output of the converter therefore a balanced output phase to phase is required but more importantly phase to neutral is also required, with the NeuTek option this can be achieved.

          
 Castle rock  POLYPHAZ converter                                            Mobile bottling plant

 
                    Inside mobile bottling plant